While trying to integrate PSE and Micrologic 2.0E, I always get FALSE TRIP status from one of the Micrologic that is installed ( ACB INCOMING UPS).
[You must be registered and logged in to see this image.]
I try to find the register list of micrologic and found that TRIP status is in register number 661 bit 2
[You must be registered and logged in to see this image.]
I try to check the register by using modscan software and the register ( register 661) is giving the TRIP status ( bit 2 = 1).
[You must be registered and logged in to see this image.]
I try to compare it with another normal micrologic and there is no TRIP status ( bit 2 = 0).
[You must be registered and logged in to see this image.]
I check the device and there is no sign of TRIP .
I also reset the micrologic by pressing the reset button but I still get the False TRIP status in PSE and in modscan
[You must be registered and logged in to see this image.]
From data above, I can conclude that the source of False TRIP status is from the Micrologic.
What should I do to fix this case?
Looking forward for your answer
Best Regards,
Timotheus Steven Gunawan
[You must be registered and logged in to see this image.]
I try to find the register list of micrologic and found that TRIP status is in register number 661 bit 2
[You must be registered and logged in to see this image.]
I try to check the register by using modscan software and the register ( register 661) is giving the TRIP status ( bit 2 = 1).
[You must be registered and logged in to see this image.]
I try to compare it with another normal micrologic and there is no TRIP status ( bit 2 = 0).
[You must be registered and logged in to see this image.]
I check the device and there is no sign of TRIP .
I also reset the micrologic by pressing the reset button but I still get the False TRIP status in PSE and in modscan
[You must be registered and logged in to see this image.]
From data above, I can conclude that the source of False TRIP status is from the Micrologic.
What should I do to fix this case?
Looking forward for your answer
Best Regards,
Timotheus Steven Gunawan